Pressure switch DUNGS GW 500 A4 HP
254285 - Setting range 0,1 - 0,5 bar
Technical data:
Setting range: 0,1 - 0,5 bar
P max.: 2 @ 0,1 - 0,15 bar / 5 @ 0,15 - 0,5 bar
Ambient temperature: -15 °C ... +70 °C
Medium temperature: -15 °C ... +70 °C
Storage temperature: -30 °C ... +80 °C
Pressure connection: p+: centrally on underside of housing internal thread G 1/4 and Rp 1/4, Gas or air
Electrical connection: Plug connection for line sockets as pert DIN EN 175 301-803, 3-pin with protection contact
Setting tolerance: ±15% switch point deviation based on the setpoint and with unit installed in a vertical position
Vent Limiter: Permissible deviation of the set value #x2264; ± 15 % in the service life test according to EN 1854
Switching difference: p min. #x2264; 0,03 bar / p max. #x2264; 0,03 bar
Adjustment: With rising pressure and installed in a vertical position. Optional rising or dropping pressure adjustment on-site possible. Note switch point change if installation position changes..
Eigenschaft |
Wert |
Original / Alternative |
Original / genuine (OE) |